Building
Inspection Report
2190 TEMPLE, WINTER PARK FLORIDA 32789,
Inspection Date:
06/03/2003
Prepared For:
GINNY ENSTAD
Prepared By:
Central Florida Home and Mold Inspections Inc Inc.
12472
Lake Underhill Drive #106
Orlando
Florida 32828
407-207-9989
407-282-0966
Fax
Report Number:
2003-1300
Inspector:
PAUL LAMBERT SCBC
035169
Report Overview
THE HOUSE IN PERSPECTIVE
CONVENTIONS USED IN THIS REPORT
For your convenience, the following conventions have been
used in this report.
Major
Concern: a system or component which is considered significantly deficient
or is unsafe. Significant deficiencies need to be corrected and, except for
some safety items, are likely to involve significant expense.
Safety
Issue: denotes a condition that is
unsafe and in need of prompt attention.
Repair:
denotes a system or component which is missing or which needs corrective action
to assure proper and reliable function.
Improve: denotes improvements which are recommended
but not required.
Monitor: denotes a system or component needing
further investigation and/or monitoring in order to determine if repairs are necessary.
Please note that those observations listed under
“Discretionary Improvements” are not essential repairs, but represent logical
long term improvements.
IMPROVEMENT RECOMMENDATION HIGHLIGHTS / summary
The following is a synopsis of the potentially significant
improvements that should be budgeted for over the short term. Other significant improvements, outside the
scope of this inspection, may also be necessary. Please refer to the body of this report for further details on
these and other recommendations.
Foundation
·
Monitor: Common minor settlement cracks were
observed in the foundation walls. This implies that some structural movement of
the building has occurred. Cracks of this type should be watched for any sign
of additional movement. In the absence of any sign of ongoing movement, repair
should not be necessary.
Floors
·
Monitor: Minor unevenness was observed in the
floor structure in various locations. This condition is common. It may be the
result of the materials, framing design, installation methods and age of the
building. There was not evidence of need for immediate, costly repair.
Exterior Walls
·
Monitor: Typical minor cracks were observed in
the exterior walls in various locations. Repairs can be deferred.
Wood Boring Insects
·
Monitor: This home is in an area known for
termite activity. Termites can do a substantial amount of damage to the wood
structural components of a home. Any form of wood/soil contact should be
avoided. Controlling dampness in the soil around the perimeter of a home,
including below porches and in crawl spaces, is recommended. Preventive
chemical treatment, performed by a licensed pest control specialist, is also
advised.
·
Monitor: The roofing is in good condition. This
roofing is wearing at uneven rates. The sides of the roof exposed to most
sunlight wear more quickly than the shaded areas. Early repair or replacement
may be needed in some areas prior to replacing the entire roof covering.
Exterior Walls
·
Monitor: Typical minor cracks were observed in
the exterior walls. Repairs can be deferred.
Exterior Eaves
·
Repair: The soffit and fascia (the wooden board
to which the gutter is typically fastened) should be painted.
Outlets
·
Repair: Ungrounded 3-prong outlets at new bath
and kitchen should be repaired. In some cases a ground wire may be present in
the electrical box and simply needs to be connected. If no ground is present
“repair” can be as simple as filling the ground slot with epoxy. Having a
ground increases safety. A grounded circuit could be strung to this outlet. A
separate ground wire could be connected. Some electrical codes allow the
installation of a ground fault circuit interrupter (GFCI) outlet where
grounding is not provided. In this case the GFCI may work but can’t be tested
by normal means.
Fixtures
·
Repair: The bathtub enclosure wall at shower is
saturated with water and mold is apparent throughout, should be rebuilt. Wall
damage behind the enclosure should also be repaired. All molded drywall and
wood needs to be removed during repair.
·
Monitor,
Repair: Water damage was noted at
bathroom wall.
·
Monitor: Damage to the interior finish was observed
at bathroom wall.
·
Monitor: Signs of mildew were observed at
bathroom wall.
·
Improve: Pool will need to be re-surfaced in the near
future.
·
Repair: Pool heater not working.
·
Repair: Pool air fan not working.
Environmental Issues
·
Monitor: There is the potential for lead content
in the drinking water within the home. Lead in water may have two sources; the
piping system of the utility delivering water to the house and/or the solder
used on copper pipes prior to 1988. This can only be confirmed by laboratory
analysis. An evaluation of lead in water is beyond the scope of this
inspection. For more information, consult the Environmental Protection Agency
(E.P.A.) for further guidance and a list of testing labs in your area.
·
Monitor: Lead based paint was in use until
approximately 1978. According to the Federal Department of Housing and Urban
Development, a lead hazard can be present in a house of this age. This can only
be confirmed by laboratory analysis. An evaluation of lead in paint is beyond
the scope of this inspection. For more information, consult the Environmental
Protection Agency (E.P.A.) for further guidance and a list of testing labs in
your area.
·
Monitor: Radon gas is a naturally occurring gas
that is invisible, odorless and tasteless. A danger exists when the gas
percolates through the ground and enters a tightly enclosed structure (such as
a home). Long-term exposure to high levels of radon gas can cause cancer. The
Environmental Protection Agency (E.P.A.) states that a radon reading of more
than 4.0 picocuries per liter of air represents a health hazard. A
radon evaluation is beyond the scope of this inspection (unless specifically
requested). For more information, consult the E.P.A. for further guidance and a
list of testing labs in your area.
THE SCOPE OF THE INSPECTION
All components designated for inspection in the ASHIâ Standards of Practice are inspected, except as may be
noted in the “Limitations of Inspection” sections within this report.
It is the goal of the inspection to put a home buyer in a
better position to make a buying decision.
Not all improvements will be identified during this inspection. Unexpected repairs should still be
anticipated. The inspection should not
be considered a guarantee or warranty of any kind.
Please refer to the pre-inspection
contract for a full explanation of the scope of the inspection.
Structure
description of Structure
Foundation: ·Concrete
Block ·Crawl Space Configuration
Floor Structure: ·Wood
Joist
Wall Structure: ·Masonry
Ceiling Structure: ·Joist ·Rafters
Roof Structure: ·Rafters ·Solid Plank Sheathing
Positive Attributes
The construction of the home is good quality. The materials
and workmanship, where visible, are good.
Exterior wall construction is solid masonry. The visible joist spans appear to be within typical construction
practices. The inspection did not
discover evidence of substantial structural movement. The construction of the house is of average quality. Typical
liberties were taken with good building practice and the quality of material
used. The inspection did not disclose significant deficiencies in the
structure. Typical minor flaws were
detected in the structural components of the building.
recommendations / observations
Foundation
·
Monitor: Common minor settlement cracks were
observed in the foundation walls. This implies that some structural movement of
the building has occurred. Cracks of this type should be watched for any sign
of additional movement. In the absence of any sign of ongoing movement, repair
should not be necessary.
Floors
·
Monitor: Minor unevenness was observed in the
floor structure in various locations. This condition is common. It may be the
result of the materials, framing design, installation methods and age of the
building. There was not evidence of need for immediate, costly repair.
Exterior Walls
·
Monitor: Typical minor cracks were observed in
the exterior walls in various locations. Repairs can be deferred.
Wood Boring Insects
·
Monitor: This home is in an area known for
termite activity. Termites can do a substantial amount of damage to the wood
structural components of a home. Any form of wood/soil contact should be
avoided. Controlling dampness in the soil around the perimeter of a home,
including below porches and in crawl spaces, is recommended. Preventive
chemical treatment, performed by a licensed pest control specialist, is also
advised.
limitations of Structure
inspection
As we have discussed and as described in your inspection
contract, this is a visual inspection limited in scope by (but not restricted
to) the following conditions:
·
Structural components concealed behind finished
surfaces could not be inspected.
·
Only a representative sampling of visible structural
components were inspected.
·
Furniture and/or storage restricted access to some
structural components.
·
Engineering or architectural services such as calculation
of structural capacities, adequacy, or integrity are not part of a home
inspection.
Please also refer to the pre-inspection
contract for a detailed explanation of the scope of this inspection.
Roofing
description of Roofing
Roof Covering:
Roof Flashings: ·Metal ·Roofing Material (Shingles) ·Aluminum
Method of Inspection: ·Viewed from ladder at
eave
Positive Attributes
The roof coverings are in generally good condition. Where investigated, eave protection has been
installed below the sloped roof coverings. This reduces the risk of roof
leakage, should ice damming develop in the winter. The steep pitch of the roof should result in a longer than normal
life expectancy for roof coverings.
General Comments
In all, the roof coverings show evidence of normal wear and
tear for a home of this age.
recommendations / observations
·
Monitor: The roofing is in good condition. This
roofing is wearing at uneven rates. The sides of the roof exposed to most
sunlight wear more quickly than the shaded areas. Early repair or replacement
may be needed in some areas prior to replacing the entire roof covering.
limitations of Roofing
inspection
As we have discussed and as described in your inspection
contract, this is a visual inspection limited in scope by (but not restricted
to) the following conditions:
·
Not all of the underside of the roof sheathing is
inspected for evidence of leaks.
·
Evidence of prior leaks may be disguised by interior
finishes.
·
Estimates of remaining roof life are approximations
only and do not preclude the possibility of leakage. Leakage can develop at any
time and may depend on rain intensity, wind direction, ice build up, and other
factors.
·
Antennae, chimney/flue interiors which are not readily
accessible are not inspected and could require repair.
·
Roof inspection may be limited by access, condition,
weather, or other safety concerns.
Please also refer to the pre-inspection
contract for a detailed explanation of the scope of this inspection.
Exterior
description of Exterior
Wall Covering: ·Block
Eaves, Soffits, And Fascias: ·Aluminum
Exterior Doors: ·Metal
Window/Door Frames and Trim: ·Metal-Covered
Entry Driveways: ·Concrete
Entry Walkways And Patios: ·Concrete
Porches, Decks, Steps, Railings: ·Concrete
Surface Drainage: ·Level Grade
Fencing: ·Wood
Window frames are clad, for the most part, with a low
maintenance material.
Positive Attributes
Window frames are clad, for the most part, with a low
maintenance material.
There is no significant wood/soil contact around the
perimeter of the house, thereby reducing the risk of insect infestation or
rot.
General Comments
The exterior of the home is generally in good
condition. The exterior shows normal
wear and tear for a home of this age.
recommendations / observations
Exterior Walls
·
Monitor: Typical minor cracks were observed in
the exterior walls. Repairs can be deferred.
Exterior Eaves
·
Repair: The soffit and fascia (the wooden board
to which the gutter is typically fastened) should be painted.
limitations of Exterior
inspection
As we have discussed and as described in your inspection
contract, this is a visual inspection limited in scope by (but not restricted
to) the following conditions:
·
A representative sample of exterior components was
inspected rather than every occurrence of components.
·
The inspection does not include an assessment of
geological, geotechnical, or hydrological conditions, or environmental hazards.
·
Screening, shutters, awnings, or similar seasonal
accessories, fences, recreational facilities, outbuildings, seawalls,
break-walls, docks, erosion control and earth stabilization measures are not
inspected unless specifically agreed-upon and documented in this report.
Please also refer to the pre-inspection
contract for a detailed explanation of the scope of this inspection.
Electrical
description of Electrical
Size of Electrical Service: ·120/240 Volt Main Service
- Service Size: 200 Amp
Service Drop: ·Overhead
Service Entrance Conductors: ·Aluminum
Service Equipment &
Main Disconnects: ·Main Service Rating 200
Amps ·Breakers
Service Grounding: ·Ground Rod Connection
Service Panel &
Overcurrent Protection: ·Breakers
Distribution Wiring: ·Copper · Non-Metallic Cable "Romex"
Switches & Receptacles: ·Grounded
and Ungrounded
Positive Attributes
The size of the electrical service is sufficient for typical
single family needs. The electrical
panel is arranged well and all fuses/breakers are properly sized. Generally speaking, the electrical system is
in good order. The distribution of
electricity within the home is good. Split
receptacles are present in the kitchen.
These outlets offer an added level of convenience, as there are separate
circuits provided for each half of the outlet.
Dedicated 220 volt circuits have been provided for all 220 volt
appliances within the home. The
majority of the old wiring within the home appears to have been updated,
improving the safety of the system at addition.
recommendations / observations
Outlets
·
Repair: Ungrounded 3-prong outlets at new bath
and kitchen should be repaired. In some cases a ground wire may be present in
the electrical box and simply needs to be connected. If no ground is present
“repair” can be as simple as filling the ground slot with epoxy. Having a
ground increases safety. A grounded circuit could be strung to this outlet. A
separate ground wire could be connected. Some electrical codes allow the
installation of a ground fault circuit interrupter (GFCI) outlet where
grounding is not provided. In this case the GFCI may work but can’t be tested
by normal means.
limitations of Electrical
inspection
As we have discussed and as described in your inspection
contract, this is a visual inspection limited in scope by (but not restricted
to) the following conditions:
·
Electrical components concealed behind finished
surfaces are not inspected.
·
Only a representative sampling of outlets and light
fixtures were tested.
·
Furniture and/or storage restricted access to some
electrical components which may not be inspected.
·
The inspection does not include remote control devices,
alarm systems and components, low voltage wiring, systems, and components,
ancillary wiring, systems, and other components which are not part of the
primary electrical power distribution system.
Please also refer to the pre-inspection
contract for a detailed explanation of the scope of this inspection.
Cooling
/ Heat Pumps
description of Cooling
/ Heat Pumps
Energy Source: ·Electricity ·240 Volt Power Supply
·Air
Source Heat Pump System
Other Components: ·Air Handler/Fan
Cooling / Heat Pumps observations
Positive Attributes
The capacity and configuration of the system should be
sufficient for the home. This is a relatively
new system that should have years of useful life remaining. Regular maintenance will, of course, be
necessary. The heat pump serves to
air-condition or cool the home and also provide heat during cooler weather
conditions. Upon testing in the air conditioning
mode, a normal temperature drop across the evaporator coil was observed. This suggests that the system is operating
properly. The location of the return
air vents is well suited to air conditioning.
The system responded properly to operating controls.
General Comments
The system shows no visible evidence of major defects.
recommendations / observations
limitations of Cooling
/ Heat Pumps inspection
As we have discussed and as described in your inspection
contract, this is a visual inspection limited in scope by (but not restricted
to) the following conditions:
·
Window mounted air conditioning units are not
inspected.
·
The cooling supply adequacy or distribution balance are
not inspected.
Please also refer to the pre-inspection
contract for a detailed explanation of the scope of this inspection.
Insulation
/ Ventilation
description of Insulation
/ Ventilation
Attic Insulation:
Roof Cavity Insulation: ·R5 Mineral Wool in Flat
Roof
Vapor Retarders: ·Kraft
Paper
Roof Ventilation: ·Ridge Vents
Exhaust Fan/vent Locations: ·Bathroom ·Cooktop Down Draft
Insulation / Ventilation observations
Positive Attributes
Insulation levels are typical for a home of this age and
construction.
recommendations / Energy saving Suggestions
Attic / Roof
·
Insulation improvements may be cost effective,
depending on the anticipated term of ownership.
limitations of Insulation
/ Ventilation inspection
As we have discussed and as described in your inspection
contract, this is a visual inspection limited in scope by (but not restricted
to) the following conditions:
·
Insulation/ventilation type and levels in concealed
areas are not inspected. Insulation and vapor barriers are not disturbed and no
destructive tests (such as cutting openings in walls to look for insulation)
are performed.
·
Potentially hazardous materials such as Asbestos and Urea
Formaldehyde Foam Insulation (UFFI) cannot be positively identified without a
detailed inspection and laboratory analysis.
This is beyond the scope of the inspection.
·
An analysis of indoor air quality is not part of our
inspection unless explicitly contracted-for and discussed in this or a separate
report.
·
Any estimates of insulation R values or depths are
rough average values.
Please also refer to the pre-inspection
contract for a detailed explanation of the scope of this inspection.
Plumbing
description of Plumbing
Water Supply Source: ·Public Water Supply
Service Pipe to House: ·Plastic
Interior Supply Piping: ·Plastic
Waste System: ·Private
Sewage System
Drain, Waste, & Vent Piping: ·Plastic
Water Heater: ·Electric ·Approximate Capacity (in gallons):
Positive Attributes
Some of the plumbing fixtures within the home have been
upgraded. The plumbing fixtures appear
to have been well-maintained. The water
heater is a relatively new unit. As the
typical life expectancy of water heaters is 7 to 12 years, this unit should
have several years of remaining life.
General Comments
The plumbing system requires some typical minor
improvements. The water heater
temperature should be set so that accidental scalding is minimized. Families with small children should be
especially aware of this issue.
recommendations / observations
Fixtures
·
Repair: The bathtub enclosure wall at shower is
saturated with water and mold is apparent throughout, should be rebuilt. Wall
damage behind the enclosure should also be repaired.
limitations of Plumbing
inspection
As we have discussed and as described in your inspection
contract, this is a visual inspection limited in scope by (but not restricted
to) the following conditions:
·
Portions of the plumbing system concealed by finishes
and/or storage (below sinks, etc.), below the structure, or beneath the ground
surface are not inspected.
·
Water quantity and water quality are not tested unless
explicitly contracted-for and discussed in this or a separate report.
·
Clothes washing machine connections are not inspected.
·
Interiors of flues or chimneys which are not readily
accessible are not inspected.
·
Water conditioning systems, solar water heaters, fire
and lawn sprinkler systems, and private waste disposal systems are not
inspected unless explicitly contracted-for and discussed in this or a separate
report.
Please also refer to the pre-inspection
contract for a detailed explanation of the scope of this inspection.
Interior
description of Interior
Wall And Ceiling Materials: ·Drywall ·Plaster
Floor Surfaces: ·Vinyl/Resilient ·Wood
Window Type(s) & Glazing: ·Sliders ·Single Pane
Doors: ·Wood-Hollow
Core
General Condition of Interior
Finishes
On the whole, the interior finishes of the home are to be in
average condition. Typical flaws were
observed in some areas.
General Condition of Windows
and Doors
The majority of the doors and windows are average quality
units.
recommendations / observations
Wall / Ceiling Finishes
·
Monitor,
Repair: Water damage was noted at
bathroom wall.
·
Monitor: Damage to the interior finish was
observed at bathroom wall.
·
Monitor: Signs of mildew were observed at
bathroom wall.
Environmental Issues
·
Monitor: There is the potential for lead content
in the drinking water within the home. Lead in water may have two sources; the
piping system of the utility delivering water to the house and/or the solder
used on copper pipes prior to 1988. This can only be confirmed by laboratory
analysis. An evaluation of lead in water is beyond the scope of this
inspection. For more information, consult the Environmental Protection Agency
(E.P.A.) for further guidance and a list of testing labs in your area.
·
Monitor: Lead based paint was in use until
approximately 1978. According to the Federal Department of Housing and Urban
Development, a lead hazard can be present in a house of this age. This can only
be confirmed by laboratory analysis. An evaluation of lead in paint is beyond
the scope of this inspection. For more information, consult the Environmental
Protection Agency (E.P.A.) for further guidance and a list of testing labs in
your area.
·
Monitor: Radon gas is a naturally occurring gas
that is invisible, odorless and tasteless. A danger exists when the gas percolates
through the ground and enters a tightly enclosed structure (such as a home).
Long-term exposure to high levels of radon gas can cause cancer. The
Environmental Protection Agency (E.P.A.) states that a radon reading of more
than 4.0 picocuries per liter of air represents a health hazard. A
radon evaluation is beyond the scope of this inspection (unless specifically
requested). For more information, consult the E.P.A. for further guidance and a
list of testing labs in your area.
limitations of Interior
inspection
As we have discussed and as described in your inspection
contract, this is a visual inspection limited in scope by (but not restricted
to) the following conditions
·
Furniture, storage, appliances and/or wall hangings are
not moved to permit inspection and may block defects.
·
Carpeting, window treatments, central vacuum systems,
household appliances, recreational facilities, paint, wallpaper, and other
finish treatments are not inspected.
Please also refer to the pre-inspection
contract for a detailed explanation of the scope of this inspection.
Appliances
description of Appliances
Appliances Tested: ·Electric Range ·Built-in Electric Oven
·Microwave
Oven ·Waste Disposer ·Dishwasher ·Refrigerator
Laundry Facility: ·240 Volt Circuit for
Dryer ·Dryer Vented to Building
Exterior ·120 Volt Circuit for
Washer ·Hot and Cold Water Supply
for Washer ·Waste Standpipe for
Washer
Other Components Tested: ·Cooktop Exhaust Vent/Fan
Positive Attributes
All appliances tested responded satisfactorily. The kitchen cabinetry is above average
quality.
General Comments
The appliances are middle aged. As such, they will become slightly more prone to breakdowns;
however, several years of serviceable life should remain.
recommendations / observations
limitations of Appliances
inspection
As we have discussed and as described in your inspection
contract, this is a visual inspection limited in scope by (but not restricted
to) the following conditions
·
Thermostats, timers and other specialized features and
controls are not tested.
·
The temperature calibration, functionality of timers,
effectiveness, efficiency and overall performance of appliances is outside the
scope of this inspection.
Please also refer to the pre-inspection
contract for a detailed explanation of the scope of this inspection.
Swimming Pool
description of SWIMMING POOL
Pool Type: ·Below
Ground Marcite
Heater: ·Gas
Heater
Filters: ·Cartridge
Filter
Pumps: ·Circulation
Pump